eprintid: 8199 rev_number: 2 eprint_status: archive userid: 1 dir: disk0/00/00/81/99 datestamp: 2023-11-09 16:20:04 lastmod: 2023-11-09 16:20:04 status_changed: 2023-11-09 16:12:02 type: article metadata_visibility: show creators_name: Shah Riman, N.I. creators_name: Abdullah, M.F. creators_name: Romlie, M.F. creators_name: Baharudin, Z. title: The third harmonic generated voltage by salient-pole synchronous generator during 3-phase�to�ground fault ispublished: pub keywords: Electric fault currents; Harmonic analysis; Natural frequencies; Poles; Synchronous generators, Excitation currents; Excitation system; Fundamental frequencies; Generator terminals; Salient pole synchronous generator; Short circuiting; Third harmonic; Zero sequences, Electric generators note: cited By 1 abstract: Conducted experiment proves that third harmonic (TH) component of salient-pole synchronous generator behaves differently compared with fundamental frequency component in terms of generated voltage. Fundamental frequency-generated voltage depends on the excitation system, and the generated voltages before and during fault are almost the same. However, TH-generated voltage is independent of the excitation system. In other words, variation of the excitation current does not affect the generation of TH voltage as much as it affects the generation of fundamental frequency voltage. On top of that, the generation of TH voltage before and during fault varies significantly. Hence, a typical method to solve fault analysis for 3-phase�to�ground fault is not applicable in TH domain. Therefore, in this article, a method to find TH-generated voltage is proposed. The TH-generated voltage during 3-phase�to�ground fault is presented in terms of percentage called the harmonic fundamental ratio, which is the ratio of TH zero-sequence�generated voltage to fundamental frequency�positive sequence-generated voltage during fault. The harmonic fundamental ratio is obtained by short circuiting the generator terminal prior to the application in the system. It turns out that the generated TH voltage by synchronous generator depends on the zero-sequence TH impedance of the TH fault current path. Lastly, the proposed method to obtain TH-generated voltage by salient-pole synchronous generator is validated by comparing the calculated TH fault current with the actual TH fault current obtained from experiment. Copyright © 2017 John Wiley & Sons, Ltd. date: 2017 publisher: John Wiley and Sons Ltd official_url: https://www.scopus.com/inward/record.uri?eid=2-s2.0-85026521065&doi=10.1002%2fetep.2401&partnerID=40&md5=1d6fbd3efcac3a235d6388dccdc24130 id_number: 10.1002/etep.2401 full_text_status: none publication: International Transactions on Electrical Energy Systems volume: 27 number: 11 refereed: TRUE issn: 20507038 citation: Shah Riman, N.I. and Abdullah, M.F. and Romlie, M.F. and Baharudin, Z. (2017) The third harmonic generated voltage by salient-pole synchronous generator during 3-phase�to�ground fault. International Transactions on Electrical Energy Systems, 27 (11). ISSN 20507038