@inproceedings{scholars2480, year = {2012}, journal = {India International Conference on Power Electronics, IICPE}, note = {cited By 6; Conference of 2012 IEEE 5th India International Conference on Power Electronics, IICPE 2012 ; Conference Date: 6 December 2012 Through 8 December 2012; Conference Code:95959}, title = {Application of custom power park to improve power quality of sensitive loads}, doi = {10.1109/IICPE.2012.6450429}, address = {Delhi}, issn = {21603162}, keywords = {Custom power park; Dynamic voltage restorer (DVR); Premium power; PSCAD/ETMDC; Shunt active power filters; Transfer switches, Computer software, Power electronics}, author = {Mohammed, B. S. and Rao, K. S. R. and Ibrahim, R. and Perumal, N.}, abstract = {This paper presents the performance of custom power devices in a Custom Power Park (CPP) by series and shunt compensation in a distribution supply system. A static transfer switch (STS) provides alternate feeder supply to park loads where shunt active power filter (SAPF), and a dynamic voltage restorer (DVR) are employed to compensate current harmonics, voltage sag, and voltage interruptions. A novel voltage detection controller based on single-phase synchronous d-q reference frame is developed which can detect single or three-phase balanced/unbalanced voltage imperfections. Extensive simulation studies are carried out by using PSCAD/EMTDC software and the ability of CPP to provide a group of customers with premium quality of power is analyzed. {\^A}{\copyright} 2012 IEEE.}, url = {https://www.scopus.com/inward/record.uri?eid=2-s2.0-84874815373&doi=10.1109\%2fIICPE.2012.6450429&partnerID=40&md5=193f02414abdd6fbb383d3cacb7cbc7a}, isbn = {9781467309318} }