%0 Journal Article %@ 10709878 %A Bakar, Norazhar Abu %A Abu-Siada, A. %D 2016 %F scholars:20462 %I Institute of Electrical and Electronics Engineers Inc. %J IEEE Transactions on Dielectrics and Electrical Insulation %K Asset management; Computer circuits; Decision making; Degradation; Electric transformer testing; Human resource management; Insulation; Oil filled transformers; Power transformers; Surface tension; Degradation process; Dielectric insulations; Furan derivatives; Fuzzy logic approach; Insulation structures; Maintenance decisions; Management decisions; Power transformer insulation; Fuzzy logic %N 5 %P 3199 – 3208 %R 10.1109/TDEI.2016.7736886 %T Fuzzy logic approach for transformer remnant life prediction and asset management decision %U https://khub.utp.edu.my/scholars/20462/ %V 23 %X The quality of insulation system within power transformer reflects the overall health condition of the asset. A timely and reliable maintenance decision along with the remaining operational life estimation of the asset can be identified through the measurements of some parameters reflecting the degradation rate of the transformer dielectric insulation. However, the process is not always straightforward due to the complexity of the insulation structure and degradation process. This paper proposes a new fuzzy logic approach to provide a proper asset management decision and predict the remaining operational life of a power transformer based on some insulating oil tests. The developed fuzzy logic model is validated through field data collected for various transformers of preknown health condition and life span. Results show that the proposed model is reliable and can be facilitated to provide a timely asset management decision with less reliance on expert personnel. © 2016 IEEE. %Z Cited by: 86