TY - JOUR VL - 22 IS - 2 SN - 10709878 JF - IEEE Transactions on Dielectrics and Electrical Insulation N2 - Interfacial tension (IFT) and acid numbers of insulating oil are correlated with the number of years that a transformer has been in service and are used as a signal for transformer oil reclamation. Oil sampling for IFT measurement calls for extra precautions due to its high sensitivity to various oil parameters and environmental conditions. The current used technique to measure IFT of transformer oil is relatively expensive, requires an expert to conduct the test and it takes long time since the extraction of oil sample, sending it to external laboratory and getting the results back. This paper introduces a new technique to estimate the IFT of transformer oil using ultraviolet-to-visible (UV-Vis) spectroscopy. UV-Vis spectral response of transformer oil can be measured instantly with relatively cheap equipment, does not need an expert person to conduct the test and has the potential to be implemented online. Results show that there is a good correlation between oil spectral response and its IFT value. Artificial neural network (ANN) approach is proposed to model this correlation. © 1994-2012 IEEE. UR - https://www.scopus.com/inward/record.uri?eid=2-s2.0-84928106451&doi=10.1109%2fTDEI.2015.7076831&partnerID=40&md5=9bdb63758c825bb0eba12e0a2a0eda65 KW - Electric transformer testing; Insulating oil; Neural networks; Oil shale; Reclamation; Surface tension; Ultraviolet visible spectroscopy; Acid numbers; Environmental conditions; Good correlations; High sensitivity; Oil parameters; Spectral response; Transformer insulation oil; UV-vis spectroscopy; Oil filled transformers ID - scholars20452 AV - none N1 - Cited by: 77 TI - A new technique to measure interfacial tension of transformer oil using UV-Vis spectroscopy Y1 - 2015/// A1 - Bakar, Norazhar Abu A1 - Abu-Siada, A. A1 - Islam, S. A1 - El-Naggar, M.F. PB - Institute of Electrical and Electronics Engineers Inc. ER -