<> "The repository administrator has not yet configured an RDF license."^^ . <> . . . "A Study of a Heat Exchanger Sizing of a Gas Turbine Inlet Air Cooling for Power Enhancement"^^ . "A gas turbine operated at the University Technology PETRONAS Gas Turbine District Cooling Plant produces an average of 3258 kWh with 30 of estimated gas turbine efficiency. A previous study done by the writer has shown of 20 increase in the efficiency of a gas turbine with the implementation of the turbine inlet air cooling. The sizing of the Heat Exchanger needed to be determined as the existing air inlet is only a 30 ft2 flange attached directly to the compressor of the gas turbine. This studies conclude that a 320 ft2 heat exchanger is needed in order to reduce the air inlet fluctuations (a range of 23�34 °C) to 15 °C. By placing the heat exchanger in the gas turbine, a significant Pa pressure loss of approximately 187.55 was experienced. © 2020, Springer Nature Singapore Pte Ltd."^^ . "2020" . . . "Springer Science and Business Media Deutschland GmbH"^^ . . "Springer Science and Business Media Deutschland GmbH"^^ . . . "Lecture Notes in Mechanical Engineering"^^ . . . "21954356" . . . . . . . . . . . . . "A."^^ . "Nordin"^^ . "A. Nordin"^^ . . "M.A.A."^^ . "Majid"^^ . "M.A.A. Majid"^^ . . "D.A."^^ . "Salim"^^ . "D.A. Salim"^^ . . . . . "HTML Summary of #13997 \n\nA Study of a Heat Exchanger Sizing of a Gas Turbine Inlet Air Cooling for Power Enhancement\n\n" . "text/html" . .